    电流是电力设备进行计量、监控和保护的重要参量,对其准确测量是电力系统安全、稳定、可靠和经济运行的保证。研制了一种Rogowski线圈、叠堆压电陶瓷和光纤Bragg光栅组合成的测量大电流的电流传感器。利用Rogowski线圈把高压侧大电流线性地转换为低电压,输出电压加在叠堆压电陶瓷上,由逆压电效应,叠堆压电陶瓷伸缩带动光纤Bragg光栅伸缩,将叠堆压电陶瓷的应变线性转换为光纤Bragg光栅的中心反射波长的移位,增加温补光栅消除环境温度的影响,通过测量光纤Bragg光栅中心反射波长的移位来测量电流的大小。测试结果表明,该电流传感器的灵敏度为0.071 8 pm/A,非线性误差为3.47%FS,滞后误差为4.17%FS,重复性误差为4.17%FS。

    Abstract:

    Current intensity is an important parameter of power equipment measurement, monitoring and protection, accurate measurement of the current intensity is the guarantee to the safeness, stableness and reliability of power system and its economic operation. A current sensor for measuring high current was developed, which a Rogowski coil, stacks of piezoelectric ceramic and fiber Bragg grating were combined together. Rogowski coil was used to put high pressure side heavy current into low voltage linearly. The output voltage was added to the stack of piezoelectric ceramic. The combined fiber Bragg grating was telescopic driven by piezoelectric ceramic stack because of the effect of inverse piezoelectric. The linear strain of piezoelectric ceramic stack was converted to the replacement of center reflective wavelength of the optical fiber Bragg grating. Temperature compensation to the fiber Bragg grating was added to eliminate the influence of environment temperature. The measurement of shift of the reflection wavelength of the fiber Bragg grating was used to measure the current. The test results showed that the sensitivity of the current sensor was 0.071 8 pm/A, the nonlinear error was 3.47% FS, the hysteresis was 4.17%FS and the repeatability was 4.17% FS.

    参考文献
    相似文献
    引证文献
引用本文

代云洪,胡明耀,王振,许晓平,李英娜,许俊飞,彭李,李川. Rogowski线圈的FBG电流传感器研究[J].压电与声光,2014,36(3):432-436. DAI Yunhong, HU Mingyao, WANG Zhen, XU Xiaoping, LI Yingna, XU Junfei, PENG Li, LI Chuan. Research of FBG Current Sensor Based on Rogowski Coil[J]. PIEZOELECTRICS AND ACOUSTOOPTICS

复制
分享
文章指标
  • 点击次数:
  • 下载次数:
  • HTML阅读次数:
历史
  • 收稿日期:
  • 最后修改日期:
  • 录用日期:
  • 在线发布日期: 2014-05-12
  • 出版日期: